How to size a generator without oversizing it

A generator has two ratings. Running (rated) watts is what it can supply all the time. Starting (surge) watts is a short burst for starting motors. Your list needs both checked.

Start with the running watts of everything that will be on at the same time. Then find the item with the biggest gap between its starting and running watts, usually a sump pump, well pump, compressor or air conditioner, and add only that gap. Motors start one at a time, so their surges do not stack. This is the method on the Lowe's wattage worksheet. Generac notes that a motor's starting draw is often two to three times its running draw.

Finally, leave room. The calculator adds 20% to the running total by default so the generator is not run at its limit and has room for appliances that draw more than chart values. That margin is our planning choice, not a manufacturer rule, and you can change it.

240 V loads and connecting to the house

Well pumps, central air, electric water heaters and large welders often run on 240 V. They need a generator with a 120/240 V outlet, and powering house circuits needs a transfer switch (or an approved interlock) installed by a licensed electrician under a permit. Never plug a generator into a dryer outlet or wall outlet: it can feed power back into the utility lines and electrocute line crews and neighbours (BC Hydro). In Canada the work falls under the Canadian Electrical Code as adopted by each province; in Ontario even homeowners doing their own wiring must file an ESA notification.

Fuel estimate method

Fuel per hour uses Honda's published EU2200i run times (0.95 US gal tank: 8.1 hours at 1/4 load, 3.2 hours at rated load), which work out to about 3.8 kWh per gallon at 1/4 load and 6.1 kWh per gallon at full load, interpolated in between. Propane is converted by energy content using the U.S. Department of Energy's figures (gasoline 112,114 to 116,090 Btu per gallon, propane 84,250 Btu per gallon) and about 4.2 lb per US gallon of liquid propane. Champion's 4500 W dual-fuel inverter claims about 22 hours at 1/4 load on 4.02 gallons, so some models use less than this estimate.

Sources

  1. Champion Power Equipment, Generator Wattage Chart: Common Appliances and Tools (page updated April 2026). Running and starting watt ranges for most items.
  2. Lowe's, Portable Generator Wattage Worksheet (2017). The running-total-plus-highest-starting method; coffee maker figure.
  3. Generac, What Size Generator Do I Need? Starting watts often two to three times running; professional load analysis for whole-home sizing.
  4. Honda, EU2200i technical specifications. Rated output, run time per tank, noise.
  5. Champion Power Equipment, 4500W Dual Fuel Open Frame Inverter (201321) specifications. Gasoline vs propane running watts, run time.
  6. U.S. Department of Energy, Alternative Fuels Data Center: Fuel Properties Comparison. Energy content of gasoline and propane.
  7. U.S. Consumer Product Safety Commission, CPSC Urges Caution When Using Portable Generators (2022). 20 ft rule, garages, porches, CO alarms, CO shut-off.
  8. Ready.gov, Power Outages: Generator Safety. 20 ft from windows, doors and attached garages; CO detectors on every level.
  9. BC Hydro, Power during outages: generators and device chargers. Backfeeding danger, CSA-approved transfer switch, permit and inspection.
  10. Electrical Safety Authority (Ontario), Can a homeowner file a notification of work?

Pages read on November 16, 2026. Garage door openers, electric kettles and shop vacs had no figure in these sources, so the calculator asks you to read their labels.

About Generator Size Calculator

Add the running watts of everything you need on at the same time, then add the extra start-up watts of the one item with the biggest surge, because motors start one at a time. Add about 20% headroom to the running total. A typical outage list (fridge, freezer, 1/2 HP sump pump, furnace blower, lights, router, TV and microwave) comes to about 4,500 W running and 5,600 W at start-up, so look for roughly 5,500 W running and 5,700 W starting.

By the ToolFluency team · Updated November 2026

Pick the appliances and tools you need to run, edit any number to match the label, and get the total running watts, the peak when the biggest motor starts, and the generator size to shop for. It flags 240 V loads that need a 120/240 V generator and a transfer switch, estimates gasoline or propane per day, and works the same in Canada and the US. Every default figure is cited in the sources below.

How to use

  1. Pick what the generator is for: Home essentials, Whole house, Jobsite or RV / camping. A typical list loads so you can see a result right away.
  2. Add the appliances and tools that will run at the same time from the list, or press Add your own item. Set the quantity of each.
  3. Check each row against the label on your own appliance or tool. The defaults are the high end of Champion's published range, shown under each item. If the label shows amps, multiply volts by amps to get watts.
  4. Read the result: running watts with everything on, the peak when the biggest motor starts, and the size to look for, with 20% headroom on the running total. Tick the box if two motors may start at the same moment.
  5. Look at the flags. 240 V items need a generator with a 120/240 V outlet and a transfer switch installed by a licensed electrician. On propane, a dual-fuel generator makes about 10% less power.
  6. Set the fuel and hours per day to see gasoline or propane use, then copy or print the load list to take to the store.

Typical generator watts (Champion Power Equipment chart, 2026)

Appliance or toolRunning wattsStarting watts
Refrigerator150 to 400800 to 1,200
Freezer100 to 500500 to 1,000
Sump pump (1/2 HP)800 to 1,0501,300 to 2,150
Well pump (1/2 HP)750 to 1,0001,500 to 2,000
Furnace fan (1/2 HP)300 to 800800 to 1,600
Window AC (10,000 BTU)900 to 1,2001,800 to 2,400
Central AC (3 ton)3,000 to 3,5005,000 to 6,000
Microwave600 to 1,200no extra
Space heater750 to 1,500no extra
Circular saw (7-1/4 in)1,200 to 1,8002,400 to 3,600
Air compressor (1 HP)1,5004,500
RV air conditioner (13,500 BTU)1,500 to 2,0002,800 to 3,500

Examples

Outage essentials in a house with a sump pump
Fridge 400 W, freezer 500 W, 1/2 HP sump pump 1,050 W, furnace blower 800 W, 10 LED bulbs 150 W, router 20 W, TV 400 W and microwave 1,200 W add up to 4,520 W running. The sump pump has the biggest extra surge (2,150 minus 1,050 = 1,100 W), so the peak is 5,620 W. With 20% headroom, look for at least 5,450 W running and 5,650 W starting.
Framing crew on a lot with no power yet
A circular saw (1,800 W), a 1 HP compressor (1,500 W), two LED work lights (50 W) and a battery charger (100 W) run 3,450 W. The compressor's extra 3,000 W start-up surge sets the peak at 6,450 W. If the compressor can kick on while the saw is starting, tick the two-motor box and the peak rises to 8,250 W.
Travel trailer with one rooftop AC
A 13,500 BTU RV air conditioner (2,000 W), RV fridge (600 W), camp lights (200 W) and a charger (100 W) run 2,900 W, and the AC start-up adds 1,500 W for a 4,400 W peak. Look for about 3,500 W running and 4,400 W starting, which is the mid-size inverter class.

Frequently asked questions

What size generator do I need to run my house in a power outage?

For the usual essentials (fridge, freezer, sump pump, furnace blower, lights, internet, TV and microwave) plan on about 5,500 W running and 5,700 W starting. Whole-house lists with central air, a well pump and an electric water heater often pass 12,000 W, which is more than most portable generators make; cut loads that do not need to run together, or have an installer size a standby generator.

Why add only the largest starting watts, not all of them?

Motors draw a short surge only while they start, and they rarely start at the exact same moment. Lowe's wattage worksheet adds the total running watts plus the one highest starting figure. Adding every surge together, as some calculators do, oversizes the generator. If two motors may start together, for example when power comes back to a whole panel, tick the two-motor box or switch loads on one at a time.

What is the difference between running watts and starting watts?

Running (rated) watts are what the generator can supply continuously. Starting (surge or peak) watts are a short burst it can give while a motor starts. Generac says a motor's starting draw is often two to three times its running figure. Generators are often sold by the bigger starting number: Champion's 4500 W dual-fuel inverter, for example, is 3,650 W running.

Can I plug a generator into a dryer outlet or wall outlet to power the house?

No. Feeding the house through an outlet with a double-ended cord can send power back into the utility lines and electrocute line crews and neighbours (BC Hydro). To run house circuits, have a licensed electrician install a transfer switch or an interlock your inspector accepts, with a permit and inspection. In Ontario, homeowners who do their own electrical work must still file an ESA notification.

How far from the house should a generator be?

Outside only, at least 20 ft (6 m) from the house, with the exhaust pointed away from doors, windows and vents (CPSC; Ready.gov). Never in a garage, basement, crawlspace or shed, even with the door open, and not on a porch or in a carport. Put CO alarms with battery backup on every level and choose a generator with automatic CO shut-off.

How much gas does a generator use per day?

It depends on the load and the model. Using Honda's EU2200i run times as the rate, a 1,000 W average load on a 3,650 W generator burns about 0.26 US gal (1 L) an hour, or about 6.1 gal (23 L) over 24 hours. On propane the same load uses about 35 lb a day, close to two 20 lb cylinders. Treat these as estimates and check your generator's run-time spec.

Should I get an inverter generator?

For RVs, camping and electronics most people choose an inverter generator. They are quieter (Honda lists the EU2200i at 53 dB at 1/4 load) and slow the engine down at light load, which saves fuel. Open-frame generators cost less per watt and suit jobsites and big home backup loads. For a CPAP or other medical device, follow the device maker's advice.

Does this work in Canada?

Yes. Canadian homes use the same 120/240 V supply as the US, so the watts and the math are the same; fuel is shown in US gallons, litres and pounds of propane. Connecting a generator to house wiring falls under the Canadian Electrical Code as adopted by your province, and needs a permit or notification (ESA in Ontario; BC Hydro notes an electrical permit and inspection in BC).
Disclaimer: This is a planning estimate, not an electrical design. Wattage varies by model, so use the label on your own appliances. Have a licensed electrician connect any generator to house wiring. Nothing on this page has been reviewed by an electrician.

Part of ToolFluency’s library of free online tools for Construction. No account needed, no data leaves your device.

Embed this tool on your site (free)
Paste this where you want the tool. Please keep the attribution link.
<iframe id="tf-generator-size-calculator" src="https://toolfluency.com/tools-v2/construction/generator-size-calculator.html?embed=1" width="100%" height="640" loading="lazy" style="border:1px solid #e2e2e2;border-radius:12px;max-width:760px" title="Generator Size Calculator by ToolFluency"></iframe>
<script>addEventListener("message",function(e){var f=document.getElementById("tf-generator-size-calculator");if(f&&e.source===f.contentWindow&&e.data&&e.data.tfEmbedHeight){f.height=e.data.tfEmbedHeight}});</script>
<p>Powered by <a href="https://toolfluency.com/tools-v2/construction/generator-size-calculator.html">Generator Size Calculator</a> — free tools by ToolFluency</p>