Garage Heater Size Calculator

Tools and materials for this job

Links go to Amazon. As an Amazon Associate, ToolFluency earns from qualifying purchases.

How to size a garage heater from its heat loss

A heater has to replace the heat the garage loses on a cold day. That loss depends on three things: how big the walls, ceiling, doors and floor edge are, how well each one is insulated, and how much colder it is outside than the temperature you want inside. Air that leaks in around the overhead door and through gaps has to be warmed too.

The calculator adds up each part. For walls, the ceiling, doors and windows it uses area x U-factor x temperature difference (a U-factor is 1 divided by the R-value). For a concrete slab it uses the perimeter method: an F-factor times the length of exposed slab edge times the temperature difference. For air leakage it uses 0.018 x air changes per hour x volume in cubic feet x the temperature difference. These are the steady-state formulas in the ASHRAE Handbook, which Ontario's Building Code (9.33.4.1) names for heating design, as laid out by Engineering ToolBox.

Which outdoor temperature to use

Size for the design temperature, not the record low. Ontario's Building Code (9.33.3.2) says to use the January 2.5% value from Supplementary Standard SB-1: a temperature that is colder only about 2.5% of the hours in January. The calculator loads all 233 places in SB-1, Table 2. In the United States, use the 99% heating dry-bulb for the nearest weather station from ASHRAE's climatic design data. Elsewhere in Canada, use the January 2.5% value in Appendix C of the National Building Code or your provincial code.

Insulation values and air leakage

R-values in the calculator are for the whole wall or ceiling, studs and all. The 2021 IECC treats R-13 batts in a 2x4 wall as U-0.084, which is about R-11.9 once the studs are counted, and an R-30 ceiling as U-0.035. Garage doors are rated by U-factor: DASMA, the door makers' association, notes that the R-value of a door section does not give the U-factor of the whole door. Air leakage is the hardest number to pin down; Modine says so and does not publish one. The Tight setting (0.5 air changes an hour) is Engineering ToolBox's rule of thumb for buildings; the Average (1) and Leaky (2) settings are our planning values, so try both ends.

Electric heaters and the circuit

Watts = BTU/h / 3.412. A 240 V heater draws its watts divided by 240 in amps. Fixed electric space heating counts as a continuous load, so the US National Electrical Code (424.4) sizes the circuit at 125% of the heater's current; that is why a 5,000 W heater (20.8 A) usually goes on a 30 A double-pole breaker. Canada's Electrical Code has its own heating rules (Section 62). Have a licensed electrician confirm the breaker, wire and disconnect; in Ontario the work needs an ESA permit, or a notification if you do your own wiring.

Gas and propane heaters

Gas heaters are sold by input: the fuel they burn. The heat you get is the output, input x efficiency. Modine's example is a 150,000 BTU/h input heater at 80% putting about 120,000 BTU/h into the space, and its Hot Dawg garage heaters are listed at up to 83%. Use a power-vented or direct-vent unit heater: Modine's manual says gas-fired heating equipment must be vented, and must not be installed where it may be exposed to a flammable atmosphere. In Ontario, fuel-fired appliances must be installed by a TSSA-registered contractor using certified gas technicians.

Sources

  1. Ontario Building Code, 2024 Compendium, Division B: 9.33.3.2 (design temperatures), 9.33.4.1 (ASHRAE and CSA F280 for heating design), 9.33.4.9 (garage contaminant transfer), 9.32.3.9A (CO alarms), and Supplementary Standard SB-1, Table 2 (January 2.5% design temperatures for 233 places).
  2. Engineering ToolBox, Heat Loss from Buildings. Transmission and infiltration formulas; 0.5 air changes an hour rule of thumb.
  3. Engineering ToolBox, Heat Transmission Loss through Building Elements. U-factors for metal and wood doors, uninsulated roofs and windows; R-5 for an uninsulated 2x4 wall.
  4. ICC, 2021 International Energy Conservation Code, Tables R402.1.2 and R402.1.3. Assembly U-factors that match R-13 and R-20 walls and R-30 and R-49 ceilings.
  5. ICC, 2021 International Energy Conservation Code, Table C402.1.4. Slab F-factors (F-0.73 uninsulated, F-0.54 with R-10 for 24 in), garage door U-0.31, swinging door U-0.37.
  6. DASMA, The Difference Between R-Value and U-Factor (2007). Garage door section R-values do not give the whole-door U-factor.
  7. Modine HVAC, How to Size a Unit Heater for Your Space. Input vs output, oversizing and short cycling, why square footage alone is not enough.
  8. Modine, gas-fired unit heaters HD and HDB, Installation and Service Manual 6-583.22 (January 2026). Venting, flammable and corrosive atmospheres, input and output ratings.
  9. Modine, Amp Dawg residential electric unit heater, Installation and Service Manual 2-529.3 (January 2026). Flammable atmospheres; wiring to NFPA 70 or CSA C22.1.
  10. TSSA, Cautions Ontario Homeowners Against Hiring Fraudulent Fuels Workers (2023) and Carbon Monoxide: What Ontarians Need to Know this Winter (2025).
  11. Electrical Safety Authority (Ontario), Can a homeowner file a notification of work?
  12. ASHRAE Climatic Design Conditions. 99% heating dry-bulb temperatures by weather station.
  13. National Research Council Canada, National Building Code of Canada 2020, Division B, Appendix C (climatic data).

Pages read on November 16, 2026. The 125% circuit rule is quoted from the National Electrical Code (NFPA 70, 424.4), which we could not open online; your electrician will apply the edition your area has adopted.

About Garage Heater Size Calculator

Work out how much heat the garage loses on the coldest design day, then buy a heater whose output covers it. An insulated 24 x 24 ft garage in Toronto (design temperature -18 °C) kept at 10 °C loses about 14,500 BTU/h (4,200 W): a 5,000 W 240 V electric heater on a 30 A circuit, or a 30,000 BTU/h input vented gas unit heater, does the job. The same garage uninsulated with a leaky door loses about 42,100 BTU/h.

By the ToolFluency team · Updated November 2026

Enter the garage size, doors, windows and insulation, pick your Ontario town (or type your own design temperature) and get the heat loss through every part of the garage in BTU/h and watts. It sizes an electric heater with the 240 V breaker and wire it typically needs, or a vented natural gas or propane unit heater by input and output. Every default value is cited in the sources below.

How to use

  1. Pick feet or metres and °C or °F. Enter the garage length, width and ceiling height. If the garage is attached, enter the length of wall it shares with the heated house.
  2. Enter the overhead garage doors, entry doors and windows, and pick the type of each. Uninsulated steel doors lose the most heat.
  3. Pick a preset (uninsulated, insulated walls only, or fully insulated), then change any surface to match your garage. Each value shows its source, and you can type your own R-value, U-factor or F-factor.
  4. Pick how leaky the garage is. Air leakage is the hardest number to estimate, so try Tight and Leaky to see the range.
  5. Choose the temperature to keep (10 °C / 50 °F for a workshop) and pick your Ontario town to fill in its January 2.5% design temperature, or type your own.
  6. Read the heat loss and the heater size. For electric, check the breaker and wire with a licensed electrician; for natural gas or propane, buy a vented unit and have a licensed gas technician install it.

Default values the calculator uses and where they come from

PartDefault valueSource
Uninsulated 2x4 wallR-5Engineering ToolBox
R-13 batts in a 2x4 wallU-0.084 (about R-11.9 whole wall)2021 IECC Table R402.1.2
R-20 batts in a 2x6 wallU-0.060 (about R-16.7)2021 IECC Table R402.1.2
Uninsulated roof, 1 in woodU-0.50 (R-2)Engineering ToolBox
R-30 ceilingU-0.035 (about R-28.6)2021 IECC Table R402.1.2
Uninsulated steel garage doorU-1.2Engineering ToolBox
Insulated garage doorU-0.312021 IECC Table C402.1.4
Entry door, wood / insulatedU-0.45 / U-0.37Engineering ToolBox / 2021 IECC
Double-glazed windowU-0.49 (2.8 W/m²K)Engineering ToolBox
Uninsulated slab edgeF-0.73 per ft of edge2021 IECC Table C402.1.4
Air leakage, tight0.5 air changes per hourEngineering ToolBox rule of thumb
Air leakage, average / leaky1 / 2 air changes per hourOur planning values

Examples

Insulated walls, R-30 ceiling, uninsulated door, Sudbury
A detached 24 x 24 ft garage with 9 ft ceilings, R-13 walls, an R-30 ceiling, one 16 x 7 ft uninsulated steel door and average air leakage, kept at 10 °C when it is -28 °C outside (a 38 °C or 68.4 °F difference). Walls 4,321, ceiling 1,379, door 9,193, slab edge 4,794 and air leakage 6,383 add up to 26,069 BTU/h (7,640 W). Electric: a 10,000 W heater on a 60 A circuit (a 7,500 W unit covers 98%). Gas at 80%: a 45,000 BTU/h input unit (about 36,000 output). The door is 35% of the loss, so insulating it first pays.
Uninsulated two-car garage in Toronto
The same 24 x 24 x 9 ft garage with no insulation, one uninsulated steel door, one entry door and leaky air sealing, kept at 10 °C on a -18 °C day, loses about 42,100 BTU/h (12,300 W). More than half of that is the bare roof and air leakage. Electric would take a 15,000 W heater; a 60,000 BTU/h input vented gas unit heater (about 48,000 output at 80%) is the other choice.
Fully insulated two-car garage in Toronto
R-13 walls, an R-30 ceiling, an insulated door (U-0.31), an insulated entry door and average leakage bring the same garage down to about 14,500 BTU/h (4,240 W). A 5,000 W 240 V heater covers it: 20.8 A, sized at 125% to 26 A, typically a 30 A double-pole breaker with 10 AWG copper.

Frequently asked questions

What size heater do I need for a two-car garage?

It depends mostly on insulation and climate. An insulated 24 x 24 ft garage in Toronto (design temperature -18 °C) kept at 10 °C loses about 14,500 BTU/h (4,200 W), so a 5,000 W electric heater covers it. The same garage with no insulation and a leaky door loses about 42,100 BTU/h (12,300 W), nearly three times as much.

How many BTU per square foot does a garage need?

There is no single number. In our Toronto examples the same 576 sq ft garage needs about 25 BTU/h per sq ft insulated and about 73 uninsulated. Modine, a unit heater maker, says square footage alone does not set heater size because insulation and air leakage change the load the most. Use a heat-loss calculation instead.

What breaker does a 5,000 W garage heater need?

5,000 W at 240 V draws 20.8 A. Fixed electric heat counts as a continuous load, so the US National Electrical Code (424.4) sizes the circuit at 125%: 26 A. That is typically a 30 A double-pole breaker with 10 AWG copper wire. Have a licensed electrician confirm it; in Canada the Canadian Electrical Code applies, and in Ontario the work needs an ESA permit or a homeowner notification.

What is the difference between input and output BTU on a gas heater?

Input is the fuel the heater burns each hour; output is the heat it delivers. Modine's example: a 150,000 BTU/h input heater at 80% efficiency puts about 120,000 BTU/h into the space. Match the output to your heat loss, not the input.

Can I heat my garage with an unvented propane heater?

Not as the heat for a closed garage or a shop. An unvented heater puts all of its exhaust, including carbon monoxide and water vapour, into the room. Modine's manual for its garage unit heaters says gas-fired heating equipment must be vented. Use a power-vented or direct-vent unit heater installed by a licensed gas technician (a TSSA-registered contractor in Ontario), and put CO alarms in the house.

What outdoor temperature should I size for?

Use the heating design temperature, not the record low. In Ontario the Building Code (9.33.3.2) requires the January 2.5% value from SB-1; the calculator has all 233 towns built in, for example Sudbury -28 °C and Toronto -18 °C. In the US use the 99% heating dry-bulb from ASHRAE climatic data. Elsewhere in Canada use the National Building Code Appendix C table.

Should I buy a bigger heater to be safe?

No. Modine warns that an oversized unit heater short-cycles: it heats too fast, shuts off and restarts, which gives uneven heat and wears the heat exchanger, ignition and fan sooner. The calculator rounds up to the next common size and no further.
Disclaimer: This is a planning estimate, not a heating design. Have a licensed electrician or gas technician confirm the heater, circuit, gas line and venting before you install anything. Nothing on this page has been reviewed by an engineer, gas technician or electrician.

Part of ToolFluency’s library of free online tools for Construction. No account needed, no data leaves your device.

Embed this tool on your site (free)
Paste this where you want the tool. Please keep the attribution link.
<iframe id="tf-garage-heater-size-calculator" src="https://toolfluency.com/tools-v2/construction/garage-heater-size-calculator.html?embed=1" width="100%" height="640" loading="lazy" style="border:1px solid #e2e2e2;border-radius:12px;max-width:760px" title="Garage Heater Size Calculator by ToolFluency"></iframe>
<script>addEventListener("message",function(e){var f=document.getElementById("tf-garage-heater-size-calculator");if(f&&e.source===f.contentWindow&&e.data&&e.data.tfEmbedHeight){f.height=e.data.tfEmbedHeight}});</script>
<p>Powered by <a href="https://toolfluency.com/tools-v2/construction/garage-heater-size-calculator.html">Garage Heater Size Calculator</a> — free tools by ToolFluency</p>