AC and Mini-Split Size Calculator

Tools and materials for this job

Links go to Amazon. As an Amazon Associate, ToolFluency earns from qualifying purchases.

How to size a room AC or a mini-split

Air conditioners are sized in BTU per hour: how much heat they can move out of a room in an hour. The simplest sizing method, and the one ENERGY STAR publishes for room air conditioners, crosses the floor area with a chart and then adjusts for sun, people and cooking.

Window and portable ACs: the ENERGY STAR chart

ENERGY STAR's chart runs from 5,000 BTU/h for 100 up to 150 sq ft to 34,000 BTU/h for 2,000 up to 2,500 sq ft, calculated for an 8 ft ceiling. Then: if the room is heavily shaded, reduce capacity by 10%; if it is very sunny, increase it by 10%; add 600 BTU/h for each person beyond two who regularly uses the room; add 4,000 BTU/h if the unit is used in a kitchen. ENERGY STAR says higher ceilings may need a bigger unit but gives no figure, so the calculator scales the area by ceiling height / 8, which is our own extension. It then rounds up to a common size sold (5,000, 6,000, 8,000, 10,000, 12,000, 14,000, 18,000 or 24,000), so it never recommends less than the ENERGY STAR figure.

ENERGY STAR also warns against oversizing: a unit that is too big costs more, wastes energy, and cools the room before it removes the humidity, leaving it damp and clammy.

Portable ACs: read the SACC

DOE's 2016 test procedure for portable air conditioners introduced the seasonally adjusted cooling capacity (SACC). It accounts for the warm outdoor air a portable pulls into the room to replace what its hose blows out, and for heat from the hose. The ASHRAE (AHAM PAC-1) number that many boxes still show leaves those out, so it is higher. Match the SACC to the size from the chart. There is no fixed conversion; it depends on the model.

Mini-splits: cooling and heating

A ductless mini-split heat pump cools in summer and heats in winter, so it has to be big enough for both. NRCan's Air-Source Heat Pump Sizing and Selection Guide sizes a heat pump for cooling at 80% to 125% of the design cooling load; the calculator uses the ENERGY STAR estimate for that load (our choice; it is an area rule, not a load calculation). For heating, it works out the heat the space loses on the design day: area x U-value x temperature difference for each wall, window and attic, the slab edge, and 0.018 x air changes per hour x volume x temperature difference for air leakage, using the same method as our garage heater calculator. Basement walls and floors below ground add Engineering ToolBox's earth resistance (0.2 + 0.3 x depth for walls, 2.0 m²K/W for floors) and still use the outdoor temperature, so basement results run high.

If the heat pump is the main heat for the space, NRCan's option 4D sizes it to the design heating load. If your baseboards or furnace stay as backup, option 4C sizes it to the load at -8.3 °C (17 °F): load x 43 / (60 - design temperature in °F). In most of Canada the heating number is the bigger one, so it sets the size.

Cold-climate heat pumps

A heat pump gives less heat as it gets colder outside. ENERGY STAR's Cold Climate designation requires a COP of at least 1.75 at 5 °F (-15 °C) and heating capacity at 5 °F of at least 70% of the capacity at 47 °F. NEEP's cold-climate product list shows each model's capacity at 5 °F. The size on the box (9,000, 12,000, 18,000 BTU) is the nominal size; check the heating capacity at your design temperature, or at 5 °F when that is the coldest figure published.

Not a load calculation

This is a room or zone estimate. It is not a CSA F280 (Canada) or ACCA Manual J (US) load calculation. ENERGY STAR says your contractor should verify a heat pump's size with Manual J. Rebate programs can ask for a load calculation: in B.C., the Home Renovation Rebate requires one for dual-fuel rebates, and the Energy Savings Program may ask for a CSA F280-12 calculation.

Who installs it

In Ontario, O. Reg. 463/10, s. 22 says no one may service or test equipment containing a refrigerant unless certified. In the US, EPA Section 608 requires certification for technicians who service equipment that could release refrigerant. Some DIY mini-split kits come with a pre-charged line set so the refrigerant circuit is never opened. The outdoor unit needs its own circuit sized from its nameplate: have a licensed electrician do it, and in Ontario get an ESA permit or file a homeowner notification.

Sources

  1. ENERGY STAR, Room Air Conditioners. The cooling capacity chart, the shade, sun, people and kitchen adjustments, the 8 ft ceiling basis, and the advice not to oversize.
  2. Natural Resources Canada, Air-Source Heat Pump Sizing and Selection Guide (2020). Cooling target 80% to 125%, sizing options 4A to 4D, the 17 °F equation, CSA F280.
  3. ENERGY STAR, Heat Pump Equipment Key Product Criteria and ENERGY STAR, Ductless Heating and Cooling. Cold Climate criteria at 5 °F; sizing with Manual J.
  4. NEEP, Cold Climate Air Source Heat Pump Specification and Product List.
  5. Carrier, How Big of a Mini Split Do I Need. The 25 BTU per sq ft estimate shown for comparison.
  6. US DOE, Test Procedures for Portable Air Conditioners, final rule (2016). SACC and the infiltration air adjustment.
  7. MMAH Supplementary Standard SB-1, Table 2 (January 2.5% design temperatures), and ASHRAE climatic design conditions.
  8. Engineering ToolBox, Heat Loss from Buildings, Building Elements: Heat Loss vs. Thermal Resistivity and Heat Transmission Loss through Building Elements.
  9. ICC, 2021 IECC Table R402.1.2 and Table C402.1.4. Wall, ceiling and slab U- and F-factors.
  10. Better Homes BC, Heat load calculation.
  11. Ontario Regulation 463/10, US EPA, Section 608 Technician Certification and Electrical Safety Authority, homeowner notification.
  12. MRCOOL DIY Select 12,000 BTU 115 V listing. A 115 V kit with a pre-charged line set.

Pages read on November 16, 2026. The ceiling scaling, the 1.0 air change value and using the ENERGY STAR area estimate as the mini-split cooling load are our own choices, labelled where they are used.

About AC and Mini-Split Size Calculator

For a window or portable AC, use ENERGY STAR's chart: about 6,000 BTU/h for 150 to 250 sq ft, 10,000 for 400 to 450, 12,000 for 450 to 550 and 14,000 for 550 to 700, with an 8 ft ceiling. Take 10% off for heavy shade, add 10% for a very sunny room, 600 BTU/h for each person beyond two and 4,000 for a kitchen, then buy the next size up. For a mini-split in Canada, check heating too: the heat loss on your winter design day often sets the size.

By the ToolFluency team · Updated November 2026

Enter the room size, ceiling height, sun, people and whether it is a kitchen. For a window or portable AC the calculator reads ENERGY STAR's sizing chart, applies its adjustments and rounds up to a common size (as SACC for portables). For a ductless mini-split heat pump it also works out the heat the space loses on your winter design day, from your Ontario town or your own design temperature, follows NRCan's heat pump sizing guide, and tells you whether heating or cooling sets the size. Every number is cited in the sources below.

How to use

  1. Pick window or portable AC, or a ductless mini-split heat pump. Pick feet or metres and °C or °F.
  2. Enter the length and width of the room, or its total area, and the ceiling height.
  3. Pick how sunny the room is, how many people are regularly in it, and tick the box if it is a kitchen.
  4. For a mini-split, pick what it will do in winter: main heat, heat with your old system as backup, or cooling only.
  5. For the heating check, enter the outside wall length, insulation, windows, what is above and below, and your Ontario town or design temperature.
  6. Read the size to buy, which of heating or cooling set it, and whether you need a cold-climate model. Check the model's heating capacity at -15 °C (5 °F) before you buy.

ENERGY STAR room air conditioner sizing chart (8 ft ceiling)

Area to be cooled (sq ft)Capacity needed (BTU per hour)
100 up to 1505,000
150 up to 2506,000
250 up to 3007,000
300 up to 3508,000
350 up to 4009,000
400 up to 45010,000
450 up to 55012,000
550 up to 70014,000
700 up to 1,00018,000
1,000 up to 1,20021,000
1,200 up to 1,40023,000
1,400 up to 1,50024,000
1,500 up to 2,00030,000
2,000 up to 2,50034,000

Examples

11 x 13 ft bedroom, very sunny, window AC
143 sq ft is in ENERGY STAR's 100 up to 150 sq ft row: 5,000 BTU/h. Very sunny adds 10%: 5,500. Two people add nothing. The next common size up is 6,000, so buy a 6,000 BTU window air conditioner.
18 x 24 ft kitchen and living room, very sunny, 4 people
432 sq ft is in the 400 up to 450 row: 10,000 BTU/h. Very sunny +10% = 11,000. Four people is two beyond two: +1,200. The kitchen adds 4,000. Total 16,200 BTU/h, so buy an 18,000 BTU window unit, and check the plug: units that big are often 230 V. A portable would need 18,000 BTU SACC, which is hard to find; a mini-split is the other option.
600 sq ft basement suite in Ottawa, mini-split as the main heat
30 x 20 ft, 8 ft ceiling, 2 ft of wall above ground, 100 ft of outside wall with R-13 batts, 16 sq ft of double-glazed windows, the house heated above, 0.5 air changes an hour, 22 °C inside and -25 °C outside (OBC SB-1). Cooling: 14,000 BTU/h for 550 up to 700 sq ft, heavily shaded -10% = 12,600; NRCan's 80% to 125% range is 10,080 to 15,750, so 12,000 covers cooling. Heating: wall above ground 1,308, windows 667, wall below ground 3,142, basement floor 4,470, air leakage 3,655, total about 13,240 BTU/h. 12,000 does not cover it, so heating sets the size: an 18,000 BTU cold-climate mini-split whose heating capacity at -15 °C (5 °F) is at least 13,240 BTU/h.

Frequently asked questions

What size air conditioner do I need for a 12 x 14 room?

A 12 x 14 ft room is 168 sq ft. ENERGY STAR's chart gives 6,000 BTU/h for 150 up to 250 sq ft with an 8 ft ceiling. Take 10% off if the room is heavily shaded, add 10% if it is very sunny, add 600 BTU/h for each person beyond two and 4,000 BTU/h for a kitchen, then buy the next common size up. With normal sun and two people, a 6,000 BTU unit.

How many BTU do I need for a 500 sq ft room?

ENERGY STAR's chart gives 12,000 BTU/h for 450 up to 550 sq ft with an 8 ft ceiling. If the room is very sunny, add 10% to get 13,200, and buy a 14,000 BTU unit. Add 600 for each person beyond two and 4,000 if it is a kitchen.

What does SACC mean on a portable air conditioner?

SACC is the seasonally adjusted cooling capacity from DOE's 2016 portable AC test. It counts the warm outdoor air a portable pulls into the room and the heat from its hose, so it is lower than the ASHRAE number many boxes also show. Match the SACC to the size from a sizing chart. There is no fixed conversion between the two numbers.

What size mini-split do I need for a 600 sq ft basement?

It depends on whether the heat pump heats the space. For a 600 sq ft basement suite in Ottawa with R-13 walls, 2 ft of wall above ground and the house heated above, cooling alone needs 12,000 BTU, but the heat loss on the -25 °C design day is about 13,200 BTU/h, so heating sets the size: an 18,000 BTU cold-climate mini-split whose heating capacity at -15 °C covers that loss. In Toronto (-18 °C) the loss is about 11,300 BTU/h and a 12,000 BTU unit fits both.

Why does heating set the mini-split size in Canada?

In most of Canada the heat a space loses on the coldest design day is bigger than the heat it gains in summer. NRCan's heat pump sizing guide sizes a heat pump that is the main heat to the design heating load, and one with backup heat to the load at -8.3 °C (17 °F). A heat pump also gives less heat as it gets colder, so check its capacity at -15 °C (5 °F), not the size on the box.

Is a bigger air conditioner better?

No. ENERGY STAR says an oversized air conditioner costs more to buy, wastes energy and does not cool better: it cools the room before it removes the humidity, so the room feels damp and clammy. Buy the next common size up from the estimate and no bigger.

Can I install a mini-split myself?

Only the parts the law allows. Refrigerant work needs a certified technician: in Ontario, O. Reg. 463/10 says no one may service equipment containing refrigerant without a certificate, and in the US it is EPA Section 608. Some DIY kits ship with a pre-charged line set so you never open the refrigerant circuit. The circuit needs a licensed electrician; in Ontario, an ESA permit or a homeowner notification.
Disclaimer: This is a room or zone estimate to help you shop. It is not a CSA F280 (Canada) or ACCA Manual J (US) load calculation, which whole-house systems and many rebate programs need. Basement heat loss is on the high side. Refrigerant work needs a certified technician and the circuit a licensed electrician. No one has reviewed this page for your home.

Part of ToolFluency’s library of free online tools for Construction. No account needed, no data leaves your device.

Embed this tool on your site (free)
Paste this where you want the tool. Please keep the attribution link.
<iframe id="tf-ac-size-calculator" src="https://toolfluency.com/tools-v2/construction/ac-size-calculator.html?embed=1" width="100%" height="640" loading="lazy" style="border:1px solid #e2e2e2;border-radius:12px;max-width:760px" title="AC and Mini-Split Size Calculator by ToolFluency"></iframe>
<script>addEventListener("message",function(e){var f=document.getElementById("tf-ac-size-calculator");if(f&&e.source===f.contentWindow&&e.data&&e.data.tfEmbedHeight){f.height=e.data.tfEmbedHeight}});</script>
<p>Powered by <a href="https://toolfluency.com/tools-v2/construction/ac-size-calculator.html">AC and Mini-Split Size Calculator</a> — free tools by ToolFluency</p>