Power Station Size Calculator

Tools and materials for this job

Links go to Amazon. As an Amazon Associate, ToolFluency earns from qualifying purchases.

Watt-hours for the outage, watts for the moment

Power stations are rated in watt-hours. Add up each device’s average watts times the hours it runs, then divide by 0.85, because some energy is lost turning battery power into household AC. That 85% figure is Anker SOLIX’s rule of thumb; we found no government or standards figure, so it is shown as an editable assumption. A fridge’s average is far below its running watts because the compressor cycles: the EnerGuide (Canada) or EnergyGuide (US) label gives kWh a year, and kWh x 1000 / 8,760 is the average in watts.

The station also needs enough output for everything that may be on at once and enough surge to start the biggest motor. Those running and starting figures come from Champion’s wattage chart, the same list the Generator Size Calculator uses. Past 5,000 Wh (our own cut-off), or with a sump pump or furnace for days, a generator is the usual answer and the calculator sends your list to it. Powering a cabin every day is a different job: use the Off-Grid Solar Calculator.

How long the fridge and freezer food stays safe without any backup is in the Power Outage Food Safety Calculator.

Figures we could not confirm

No published figure exists for how many hours a day a sump pump or furnace blower runs, a freezer’s average watts, or how much a battery loses in the cold. The calculator shows its starting values for these as editable assumptions and says so next to each one. For a sump pump, time your own with the Sump Pump Battery Backup Calculator.

Sources

  1. Anker SOLIX, How long will a power station last (a maker’s blog). 85% usable rule, fridge 60 W, CPAP 40 W, router 15 W, LED 10 W, phone 10 Wh a charge.
  2. Champion Power Equipment, Generator Wattage Chart. Running and starting watts.
  3. Natural Resources Canada, Reading the EnerGuide label. Annual kWh.
  4. Public Safety Canada, Get Prepared: Power outages. Power stations indoors, generator 6 m rule, after-outage steps, medical devices.
  5. Health Canada, Carbon monoxide: preventing exposure. CO alarms.
  6. CDC, Protect yourself during a power outage. Generators and CO.
  7. Ready.gov, Power Outages and CPSC, Carbon Monoxide Information Center (CPSC read through search extracts; the site blocks automated reading).
  8. ResMed support, battery use and humidification.

All pages read and checked on November 16, 2026. Not medical advice. In an emergency, call 911.

About Power Station Size Calculator

Add up each device’s average watts times the hours it runs in the outage, then divide by 0.85, because only about 85% of the rated Wh reaches AC devices (Anker SOLIX). A fridge, an internet router, two phones and four LED bulbs for 24 hours use 2,020 Wh, so look for a power station of at least 2,377 Wh and 520 W, with a surge rating of at least 1,320 W for the fridge to start: the 3,000 Wh size step.

By the ToolFluency team · Updated November 2026

Set how long the outage might last and pick what you need to keep running: the fridge, freezer, CPAP, phones, router, lights, a sump pump or furnace blower, or your own device. You get the power station size in Wh, the AC output and surge it needs in W, or how long your own station will last, plus the power bank your phones need. Lists too big for a battery go to the Generator Size Calculator. Every number cites its source.

How to size a power station for an outage

  1. Set how long the outage might last: overnight, a day, 3 days, 7 days, or your own number.
  2. Add what you need to keep running. Change the watts and hours to match your own devices. For a fridge or freezer, type the kWh a year from its EnerGuide or EnergyGuide label for a better number.
  3. Read the result: the capacity in Wh and the AC output in W to look for, and the surge rating a motor needs to start.
  4. Have a station already? Pick I have one, then type its Wh, output and surge to see how long it runs your list.
  5. Past 5,000 Wh, or a sump pump or furnace for days? Send the list to the Generator Size Calculator.
  6. Just the phones? Enter how many in the power bank box for the bank size.

Starting figures for common outage devices (Anker averages; Champion running and start-up watts)

DeviceAverage drawRunning and start-up watts
Refrigerator60 W (or label kWh a year x 1000 / 8,760)150 to 400 W running, 800 to 1,200 W to start
CPAP, no heated humidifier40 W30 to 60 W
Internet router / modem15 W10 to 20 W
LED light bulb10 W8 to 15 W
Phone10 Wh per full charge20 to 100 W charger

Examples

Fridge, internet, phones and lights for a day
A fridge at 60 W for 24 hours (1,440 Wh), an internet router at 15 W for 24 hours (360 Wh), two phones at 10 Wh a charge once a day (20 Wh) and four LED bulbs at 10 W for 5 hours (200 Wh) use 2,020 Wh. Divided by 0.85 that is 2,377 Wh, the 3,000 Wh size step. Everything on at once draws 520 W, and 1,320 W while the fridge starts.
Phones, internet and lights for a day
Two phones at 10 Wh a charge, once a day (20 Wh), an internet router at 15 W for 24 hours (360 Wh) and four LED bulbs at 10 W for 5 hours (200 Wh) use 580 Wh. Divided by 0.85 that is 683 Wh, so the 700 Wh size step. Everything on at once draws 120 W.
Fridge and CPAP overnight
A fridge at 60 W for a 10-hour outage (600 Wh) and a basic CPAP at 40 W for 8 hours (320 Wh) use 920 Wh; divided by 0.85 that is 1,083 Wh, the 1,500 Wh size step. With a 450 kWh a year label the fridge averages 51 W and the total drops to 834 Wh, or 981 Wh after losses: the 1,000 Wh size step. Output at least 460 W and surge at least 1,260 W for the compressor to start.
Three days with a sump pump and furnace
Fridge and freezer at 60 W each, a 1/2 HP sump pump at 1,050 W for 4 hours a day, a furnace blower at 800 W for 8 hours a day, a router and four LED bulbs use 14,040 Wh a day, or 42,120 Wh over 3 days. That needs 49,553 Wh of battery, far past practical power station sizes, so the list goes to the Generator Size Calculator: 2,830 W running and a 3,930 W peak as the sump pump starts.

Frequently asked questions

What size power station do I need to run a fridge?

A fridge averages about 60 W as its compressor cycles (Anker), or work it out from the EnerGuide or EnergyGuide label: kWh a year x 1000 / 8,760. Overnight with a CPAP, a fridge at 60 W for 10 hours and a basic CPAP at 40 W for 8 hours use 920 Wh; divided by 0.85 for inverter losses that is 1,083 Wh, so the 1,500 Wh size step. The station also needs enough surge to start the compressor: Champion puts a fridge at up to 1,200 W to start.

How long will a power station run a CPAP?

Divide the station rating times 0.85 by the CPAP draw. Anker puts a basic CPAP at about 40 W, so a 500 Wh station gives 500 x 0.85 / 40 = 10.6 hours. With a heated humidifier Champion lists 60 to 120 W; ResMed advises turning it off on battery. Use your device maker’s battery figure and talk to your provider.

Why divide by 0.85?

A power station loses some energy turning its battery into household AC power. Anker SOLIX’s rule of thumb is that about 85% of the rated Wh reaches AC devices. We found no government or standards figure, so the calculator shows 0.85 as an editable assumption.

What size power bank do I need for phones in an outage?

About 10 Wh charges a phone once (Anker). Two phones, one charge a day for 3 days, use 60 Wh; divided by 0.85 for charging losses that is 70.6 Wh, or 19,100 mAh at 3.7 V, so one 20,000 mAh power bank.

Can I use a power station indoors?

Yes. A battery power station makes no carbon monoxide and can be used indoors (Get Prepared). A generator, BBQ, charcoal grill or camp stove never runs indoors or in a garage, basement, crawlspace or shed, even with the door open; a portable generator goes outside at least 6 m (20 ft) from the house (Get Prepared; Health Canada).

When should I use a generator instead of a power station?

When the list is too big for a battery. A sump pump, furnace blower and fridge for 3 days use 42,120 Wh, about ten times a large power station. Past 5,000 Wh (our own cut-off), the calculator sends your list to the Generator Size Calculator.
Disclaimer: General preparedness information from Public Safety Canada, Health Canada, Ready.gov and the CDC, with device figures from Anker SOLIX and Champion, checked against those pages on 2026-11-16. The power station size steps (300 to 5,000 Wh) and the 5,000 Wh hand-off to a generator are our suggestion, not published figures. Not medical advice: if you rely on a powered medical device, make a plan with your doctor or device maker and your power utility. Local instructions come first. In an emergency, call 911.

Part of ToolFluency’s library of free online tools for Emergency Prep. No account needed, no data leaves your device.

Embed this tool on your site (free)
Paste this where you want the tool. Please keep the attribution link.
<iframe id="tf-power-station-size-calculator" src="https://toolfluency.com/tools-v2/emergency/power-station-size-calculator.html?embed=1" width="100%" height="640" loading="lazy" style="border:1px solid #e2e2e2;border-radius:12px;max-width:760px" title="Power Station Size Calculator by ToolFluency"></iframe>
<script>addEventListener("message",function(e){var f=document.getElementById("tf-power-station-size-calculator");if(f&&e.source===f.contentWindow&&e.data&&e.data.tfEmbedHeight){f.height=e.data.tfEmbedHeight}});</script>
<p>Powered by <a href="https://toolfluency.com/tools-v2/emergency/power-station-size-calculator.html">Power Station Size Calculator</a> — free tools by ToolFluency</p>